Introducing The Pyroshield Universal Actuator, Ushering in a New Age of Fire Protection, Choosing a fire suppression system, PyroStorm protection for control equipment, smoke warns AST, Cable-type heat sensing systems, Enhanced fire detection for conveyor belts, Is your building safe from fire, AST’s automated fire extinguishing systems, Room integrity testing, When there’s clouds (not smoke), there’s fire, Are the Halon Bandits back, The first 400 bar inert gas filling plant in Africa, Low pressure monitor gauge, Pyrosense3, Fire risks that affect the power generation industry, Conveyor system protection,

Conveyor belt fire protection

Conveyor belt fire protection: The movement of materials for the mining and metals industry is of critical importance to operations. A key decision is therefore the transport reliability versus the capital and operational cost of the transportation system.

Choice of the transport system

The basic decision revolves around whether trucking or conveyor systems should be used. Conveyor systems are the ideal solution to transport manageable sized material from one processing point to another, such as from an underground mine to a processing refinery. The reliance on manpower is minimised and reliability is maximised provided the correct protection measures are taken to reduce the chance of a mechanical or electrical failure.

Conveyor belt fire protection

A key protection area for consideration is how to handle the issue of a conveyor belt system fire. What questions need to be asked? What areas need consideration? What solutions are available? Are they practical solutions?

Conveyor belt fire protection is a specialised niche area where knowledge can be vague or hard to come by. Conveyor belt fires are not new: the March 1940 issue of Popular Mechanics published an article relating to a 20 mile gravel haulage conveyor system. It described the use of thermocouple hoods as means of detecting fire. Of course, there are much more effectual systems available today, but you have to hand it to those past engineers for using the best technology available at the time.

Any mechanical process is liable to failure at some point and some failures can prove catastrophic if there are no emergency systems in place to alleviate the risk. The philosophy behind conveyor belt fire protection involves the preservation of the conveyor system structure. A fire can weaken the metal structure, in some cases to the point of collapse, hence the need for early detection and extinguishing of the fire, while at the same time cooling the affected structure.

Detection methods have evolved since the thermocouple hoods of the 1940s. Fire detection companies have tried to adapt detection devices that were designed for less rugged applications and sought in the past to use them on conveyor belt systems. The uses of spark and ember detectors have been popular, but have proved largely ineffectual. The problems revolve around the potential of false alarms namely from reflective light or solar emissions. Also the monitored bandwidth that would result in an alarm is quite narrow, meaning early stage combustion cannot always be detected.

Static and moving fires

There are two primary sources of conveyor belt fires: either static heat build-up from friction caused by belt movement, over a jammed idler for example, or moving fire on the belt itself. For early detection of static type fires, Linear Heat Detection Cable has proven to be reliable when correctly installed, ideally at a height of 1-1,5 m above the belt. Tests have shown that such systems responded within two minutes to a small-sized fire.

Linear Heat Detection Cable can also be placed between the belt and return if practical. Its primary advantage is that it is easily configurable, either in zoned areas along a conveyor that can signal the belt to stop and switch on a water-spray system, or it can be integrated into a sprinkler system that uses temperature threshold bulbs to operate.

Another primary consideration is how to detect a moving fire as early as possible. The answer is to relate infrared emissions to the thermal properties of the masses. Black body radiation, of infrared emissions of a much wider spectrum compared to spark and ember detectors, can be detected when an object begins to increase in temperature. Such devices offer the capability to detect hot objects on a conveyor belt well before they begin to glow. In some cases, they can detect such objects even when buried. These types of detectors offer a reliable yet highly sensitive response to the early stages of combustion that can occur on a conveyor belt system.

Conclusion

Combined together, linear heat detection cable and thermal energy black body fire detectors offer a comprehensive solution to fire detection on conveyor belt systems. If installed properly, they can be integrated into a water extinguishing system, either a sprinkler bulb or a water-spray type.

It is only recently that fire engineers are beginning to understand the best approaches to conveyor belt fires and how to extinguish such fires. Factory Mutual, in its FM Global Property Loss Prevention Datasheet FM7-11, has put together a design matrix for selecting the appropriate type of water system for a conveyor belt system. These are excellent guidelines to mitigate against fire damage. By following the simple steps in FM7-11, in conjunction with the latest approaches in fire detection, companies can limit the damage and losses caused by conveyor belt fires.

Link to article: http://www.instrumentation.co.za/46036n